- FP 2 Zone Conventional Fire Alarm Panel has an Installer-friendly design.
- FP 2 Zone Conventional Fire Alarm Panel comes with Robust metal enclosure c/w lift off lid & heavy-duty base connections.
- It Has two conventional Zone circuits.
- It has also two conventional Sounder circuits
- FP 2 Zone Conventional Fire Alarm Panel have a Separate indicator for both open & short circuit fault, sounder fault and battery/power supply fault.
[zionhost_shortcodes_bullet_points]
| Technical Specifications | |
|---|---|
| Mains supply | 230V 50/60Hz.. |
| Internal power supply | 27V nominal.. |
| Total output current limited to | 800mA @ 230V. |
| Quiescent current | 40mA |
| Max battery size and type | 2 x 12V 2.3Ah VRLA connected in series |
| No. of detector zone circuits | (Max. length per circuit is 500m). |
| Call point resistor value | 470 to 680Ω |
| Max. devices per detector zone | 20 detectors |
| No. of conventional sounder circuits | 2 (Max. length per circuit is 500m). |
| EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
| Max. sounder output current | 800mA (to all outputs). Outputs are fused at 1A. |
| Weight | 4.3kg. |